Parallel-flow exchanger effectiveness

Effectiveness of a parallel-flow exchanger with both fluids entering at the same end, from the number of transfer units N = UA/Cmin and the capacity ratio Cr = Cmin/Cmax.

Ref
HTS-41
Rev
v1
Field
Heat transfer and thermal systems
Result
ε

In a parallel-flow exchanger both fluids enter at the same end and move together, so the outlet temperatures converge towards a common value but can never cross. The effectiveness is ε = [1 − exp(−NTU(1 + Cr))]/(1 + Cr), which cannot exceed 1/(1 + Cr), however large the NTU. NTU = UA/Cmin and Cr = Cmin/Cmax.

Effectiveness of a parallel-flow exchanger with both fluids entering at the same end, from the number of transfer units N = UA/Cmin and the capacity ratio Cr = Cmin/Cmax.

Calculator

Solve for
020
01
  • Limit at large NTU, 1/(1 + Cr)0.6667
  • Shortfall against the limit0.1488
  • Counterflow effectiveness at the same NTU and Cr0.5647

What drives the result

Each variable is moved across its typical range while the others stay at the values above. The longest bar is the key driver.

Effectiveness () current value 0.5179
NTUNumber of transfer units UA/CminKey driver
00.667
CrCapacity ratio Cmin/Cmax
0.4320.632
  • The exchanger recovers 51.79 % of the maximum possible heat transfer, and cannot exceed 66.67 % however large it is made.
  • A counterflow unit of the same size would reach 56.47 %, which is why counterflow is preferred when high effectiveness is needed.
Chart data as tables

Ranked variables

VariableTypical rangeLowest resultHighest resultSwing ()Local stepChange in result
NTU Number of transfer units UA/Cmin0 to 20 00.66670.6667+10%+4 %
Cr Capacity ratio Cmin/Cmax0 to 1 0.43230.63210.1998+10%−1.87 %

Sweep of Number of transfer units UA/Cmin

Number of transfer units UA/CminEffectiveness
00
2.50.651
50.6663
7.50.6667
100.6667
12.50.6667
150.6667
17.50.6667
200.6667

Sweep one variable

Effectiveness ()Hover, touch, or use the arrow keys on the chart
00.20.40.6 05101520 Number of transfer units UA/Cmin now 0.5179

Variables and how each one contributes

ε

Effectiveness

Result ·

What the equation gives you. Everything else feeds it.

NTU

Number of transfer units UA/Cmin

· typical 0 to 20

The number of transfer units, UA/Cmin. Raises the effectiveness, with falling returns towards the limit 1/(1 + Cr). Raising it by 10 % (to 1.1) moves the result by +4 %, from 0.5179 to 0.5386.

Cr

Capacity ratio Cmin/Cmax

· typical 0 to 1

The capacity ratio Cmin/Cmax, between 0 and 1. A larger ratio lowers the effectiveness and its limit. Raising it by 10 % (to 0.55) moves the result by −1.87 %, from 0.5179 to 0.5082.

Worked example with the values above

  1. Exponent: NTU(1 + Cr) = 1 × 1.5 = 1.5; 1 − exp(−that) = 0.77687.
  2. Divide by 1 + Cr = 1.5.
  3. ε = 0.51791.

Assumptions and limits

  • Steady operation with constant properties and overall coefficient, and an insulated exterior.
  • The flow arrangement matches the formula exactly, including which fluid is mixed.

Common mistakes

  • Using the wrong stream as Cmin when forming the capacity ratio.
  • Mixing up NTU with UA.
  • Using a counterflow formula for a parallel or crossflow unit.

Statistics and uncertainty

Effectiveness formulas are exact for their ideal arrangements, but real exchangers have bypass, leakage and non-uniform flow, which lower performance by a few per cent to 10 %. Fouling allowances are largely judgement.

Where it is used

  • Rating exchangers from known UA and flow rates.
  • Estimating the effect of fouling on duty.

Maths you need

  • Capacity rate: C = ṁcp, in W/K
  • NTU: UA divided by Cmin
  • Effectiveness: actual heat transfer over the thermodynamic maximum