Overall conductance of a fouled cylindrical tube

Overall conductance UA of a tube with convection and fouling on both sides and conduction through the wall.

Ref
HTS-45
Rev
v1
Field
Heat transfer and thermal systems
Result
UA [W/K]

The overall conductance of a tube with convection and fouling on both sides and conduction through the wall adds the resistances in series: 1/UA = (1/hi + Rfi)/Ai + ln(ro/ri)/(2πkL) + (1/ho + Rfo)/Ao, with Ai = 2πriL and Ao = 2πroL. Rfi and Rfo are area-specific fouling resistances on their own sides. UA does not depend on the reference area.

Overall conductance UA of a tube with convection and fouling on both sides and conduction through the wall. Rfi and Rfo are area-specific fouling resistances on their own sides; the answer does not depend on the reference area.

Calculator

Solve for
W/K
m
0.0050.0119
m
0.0120.05
m
0.120
W/(m² K)
1050,000
W/(m² K)
1050,000
W/(m K)
0.1500
m² K/W
00.005
m² K/W
00.005
  • Total resistance, 1/UA0.04862 K/W
  • Wall conduction resistance, ln(ro/ri)/(2πkL)0.001934 K/W
  • Share of the total resistance due to fouling0.08729

What drives the result

Each variable is moved across its typical range while the others stay at the values above. The longest bar is the key driver.

Overall conductance (W/K) current value 20.57 W/K
LTube lengthKey driver
2.06411
hoOutside coefficient
0.74244.7
hiInside coefficient
0.61630.3
kWall conductivity
2.9721.4
RfiInside fouling resistance
7.921.3
RfoOutside fouling resistance
8.9121.8
riInner radius
13.622.7
roOuter radius
24.5
  • The tube conducts 20.57 W for every kelvin between the two fluids, with 8.73 % of the resistance from fouling.
  • The wall itself accounts for 3.98 %, so the film coefficients and fouling decide the performance, not the metal.
Chart data as tables

Ranked variables

VariableTypical rangeLowest resultHighest resultSwing (W/K)Local stepChange in result
L Tube length0.1 to 20 m2.057411.4409.3+10%+10 %
ho Outside coefficient10 to 50,000 W/(m² K)0.741644.7243.98+10%+5.22 %
hi Inside coefficient10 to 50,000 W/(m² K)0.615730.2829.67+10%+3.07 %
k Wall conductivity0.1 to 500 W/(m K)2.96921.3918.42+10%+0.363 %
Rfi Inside fouling resistance0 to 0.005 m² K/W7.89921.2613.37+10%−0.326 %
Rfo Outside fouling resistance0 to 0.005 m² K/W8.90621.7512.85+10%−0.543 %
ri Inner radius0.005 to 0.0119 m13.6122.749.129+10%+5.66 %
ro Outer radius0.012 to 0.05 m20.5724.523.95+10%+3.49 %

Sweep of Outside fouling resistance

Outside fouling resistance (m² K/W)Overall conductance (W/K)
021.75
6.25e-418.43
0.0012515.99
0.00187514.12
0.002512.64
0.00312511.44
0.0037510.45
0.0043759.616
0.0058.906

Sweep one variable

Overall conductance (W/K)Hover, touch, or use the arrow keys on the chart
810121416182022 00.0010.0020.0030.0040.005 Outside fouling resistance (m² K/W) now 20.57

Variables and how each one contributes

UA

Overall conductance

Result · W/K

What the equation gives you. Everything else feeds it.

ri

Inner radius

m · typical 0.005 to 0.0119

The inner radius, in m. A larger inner radius adds inside area, so the conductance rises. Raising it by 10 % (to 0.011) moves the result by +5.66 %, from 20.57 to 21.73 W/K.

ro

Outer radius

m · typical 0.012 to 0.05

The outer radius, in m. A larger outer radius thickens the wall but adds outside area; here the net effect depends on the resistances. Raising it by 10 % (to 0.0132) moves the result by +3.49 %, from 20.57 to 21.29 W/K.

L

Tube length

m · typical 0.1 to 20

The tube length, in m. Raises UA in direct proportion. Raising it by 10 % (to 1.1) moves the result by +10 %, from 20.57 to 22.62 W/K.

hi

Inside coefficient

W/(m² K) · typical 10 to 50,000

The inside convection coefficient, in W/(m² K). A larger coefficient raises UA, with falling returns once other resistances dominate. Raising it by 10 % (to 1,100) moves the result by +3.07 %, from 20.57 to 21.2 W/K.

ho

Outside coefficient

W/(m² K) · typical 10 to 50,000

The outside convection coefficient, in W/(m² K). A larger coefficient raises UA, with falling returns once other resistances dominate. Raising it by 10 % (to 550) moves the result by +5.22 %, from 20.57 to 21.64 W/K.

k

Wall conductivity

W/(m K) · typical 0.1 to 500

The wall conductivity, in W/(m K). A higher conductivity lowers the small wall resistance. Raising it by 10 % (to 16.5) moves the result by +0.363 %, from 20.57 to 20.64 W/K.

Rfi

Inside fouling resistance

m² K/W · typical 0 to 0.005

The inside fouling resistance, in m² K/W. More fouling lowers UA. Raising it by 10 % (to 1.1×10−4) moves the result by −0.326 %, from 20.57 to 20.5 W/K.

Rfo

Outside fouling resistance

m² K/W · typical 0 to 0.005

The outside fouling resistance, in m² K/W. More fouling lowers UA. Raising it by 10 % (to 2.2×10−4) moves the result by −0.543 %, from 20.57 to 20.46 W/K.

Worked example with the values above

  1. Inside resistance (film + fouling): 0.017507 K/W; wall: 0.0019345 K/W; outside: 0.029178 K/W.
  2. Total: 0.04862 K/W.
  3. UA = 1 / 0.04862 = 20.568 W/K.

Assumptions and limits

  • Steady operation with constant properties and overall coefficient, and an insulated exterior.
  • The flow arrangement matches the formula exactly, including which fluid is mixed.

Common mistakes

  • Using the wrong stream as Cmin when forming the capacity ratio.
  • Mixing up NTU with UA.
  • Using a counterflow formula for a parallel or crossflow unit.

Statistics and uncertainty

Effectiveness formulas are exact for their ideal arrangements, but real exchangers have bypass, leakage and non-uniform flow, which lower performance by a few per cent to 10 %. Fouling allowances are largely judgement.

Where it is used

  • Rating exchangers from known UA and flow rates.
  • Estimating the effect of fouling on duty.

Maths you need

  • Capacity rate: C = ṁcp, in W/K
  • NTU: UA divided by Cmin
  • Effectiveness: actual heat transfer over the thermodynamic maximum