One-shell-pass exchanger effectiveness

Effectiveness of an ideal shell-and-tube exchanger with one shell pass and two or an even number of tube passes, with equal area per pass and no bypass or leakage.

Ref
HTS-44
Rev
v1
Field
Heat transfer and thermal systems
Result
ε

An ideal exchanger with one shell pass and two or any even number of tube passes has ε = 2/[1 + Cr + S/tanh(NTU·S/2)], with S = √(1 + Cr²). It gives zero at NTU = 0 and approaches 2/(1 + Cr + S) at large NTU, which is below 1 for Cr above zero. The model assumes equal area per pass and no bypass or leakage.

Effectiveness of an ideal shell-and-tube exchanger with one shell pass and two or an even number of tube passes, with equal area per pass and no bypass or leakage. Returns zero when NTU = 0.

Calculator

Solve for
020
01
  • Parameter, S = √(1 + Cr²)1.118
  • Limit at large NTU, 2/(1 + Cr + S)0.7639
  • Counterflow effectiveness at the same NTU and Cr0.5647

What drives the result

Each variable is moved across its typical range while the others stay at the values above. The longest bar is the key driver.

Effectiveness () current value 0.5399
NTUNumber of transfer units UA/CminKey driver
00.764
CrCapacity ratio Cmin/Cmax
0.4630.632
  • The shell-and-tube unit reaches 53.99 % effectiveness, and its ceiling at this capacity ratio is 76.39 %.
  • A true counterflow unit would get 56.47 %, so the multi-pass arrangement gives up some performance for compactness.
Chart data as tables

Ranked variables

VariableTypical rangeLowest resultHighest resultSwing ()Local stepChange in result
NTU Number of transfer units UA/Cmin0 to 20 00.76390.7639+10%+4.58 %
Cr Capacity ratio Cmin/Cmax0 to 1 0.46270.63210.1694+10%−1.55 %

Sweep of Number of transfer units UA/Cmin

Number of transfer units UA/CminEffectiveness
00
2.50.7237
50.7615
7.50.7638
100.7639
12.50.7639
150.7639
17.50.7639
200.7639

Sweep one variable

Effectiveness ()Hover, touch, or use the arrow keys on the chart
00.20.40.60.8 05101520 Number of transfer units UA/Cmin now 0.5399

Variables and how each one contributes

ε

Effectiveness

Result ·

What the equation gives you. Everything else feeds it.

NTU

Number of transfer units UA/Cmin

· typical 0 to 20

The number of transfer units, UA/Cmin. Raises the effectiveness, with falling returns. Raising it by 10 % (to 1.1) moves the result by +4.58 %, from 0.5399 to 0.5647.

Cr

Capacity ratio Cmin/Cmax

· typical 0 to 1

The capacity ratio Cmin/Cmax, between 0 and 1. A larger ratio lowers the effectiveness. Raising it by 10 % (to 0.55) moves the result by −1.55 %, from 0.5399 to 0.5316.

Worked example with the values above

  1. S = √(1 + 0.5²) = 1.118; tanh(NTU·S/2) = tanh(0.55902) = 0.50725.
  2. Denominator: 1 + Cr + S/tanh = 1.5 + 2.2041 = 3.7041.
  3. ε = 2 / 3.7041 = 0.53994.

Assumptions and limits

  • Steady operation with constant properties and overall coefficient, and an insulated exterior.
  • The flow arrangement matches the formula exactly, including which fluid is mixed.

Common mistakes

  • Using the wrong stream as Cmin when forming the capacity ratio.
  • Mixing up NTU with UA.
  • Using a counterflow formula for a parallel or crossflow unit.

Statistics and uncertainty

Effectiveness formulas are exact for their ideal arrangements, but real exchangers have bypass, leakage and non-uniform flow, which lower performance by a few per cent to 10 %. Fouling allowances are largely judgement.

Where it is used

  • Rating exchangers from known UA and flow rates.
  • Estimating the effect of fouling on duty.

Maths you need

  • Capacity rate: C = ṁcp, in W/K
  • NTU: UA divided by Cmin
  • Effectiveness: actual heat transfer over the thermodynamic maximum