Dittus–Boelter Nusselt number for heating or cooling

Turbulent Nusselt number in a smooth tube, with the exponent n = 0.4 when the fluid is heated and 0.3 when it is cooled.

Ref
HTS-29
Rev
v1
Field
Heat transfer and thermal systems
Result
NuD

The Dittus–Boelter correlation Nu = 0.023 Re^0.8 Prⁿ describes turbulent flow in a smooth tube, with n = 0.4 when the fluid is heated and 0.3 when it is cooled. This version takes n as an input, generalising the fixed heating form on the existing page. It holds for Re ≥ 10⁴, 0.7 ≤ Pr ≤ 160 and L/D ≥ 10, with bulk properties.

Turbulent Nusselt number in a smooth tube, with the exponent n = 0.4 when the fluid is heated and 0.3 when it is cooled. It generalises the fixed heating form on the existing Dittus–Boelter page. Use for Re ≥ 10⁴, 0.7 ≤ Pr ≤ 160 and L/D ≥ 10.

Calculator

Solve for
10,0001,000,000
0.7160
0.30.4
  • Nusselt number for heating (n = 0.4)230
  • Nusselt number for cooling (n = 0.3)230
  • Coefficient for water with k = 0.6 W/(m K) in a 20 mm tube6,900 W/(m² K)

What drives the result

Each variable is moved across its typical range while the others stay at the values above. The longest bar is the key driver.

Nusselt number () current value 230
PrPrandtl numberKey driver
1991,750
ReDReynolds number based on diameter
36.51,450
nExponent (0.4 heating, 0.3 cooling)
  • With n = 0.4 the Nusselt number is 230; the heating form would give 230 and the cooling form 230.
  • At Pr = 1 the exponent has no effect, since 1 to any power is 1; the heating and cooling forms differ only when Pr moves away from 1.
Chart data as tables

Ranked variables

VariableTypical rangeLowest resultHighest resultSwing ()Local stepChange in result
Pr Prandtl number0.7 to 160 199.41,7511,552+10%+3.89 %
ReD Reynolds number based on diameter10,000 to 1,000,000 36.451,4511,415+10%+7.92 %
n Exponent (0.4 heating, 0.3 cooling)0.3 to 0.4 2302300+10%0 %

Sweep of Reynolds number based on diameter

Reynolds number based on diameterNusselt number
10,00036.45
133,800290.2
257,500490.2
381,300671
505,000840.2
628,8001,001
752,5001,156
876,3001,306
1,000,0001,451

Sweep one variable

Nusselt number ()Hover, touch, or use the arrow keys on the chart
050010001500 200k400k600k800k1M Reynolds number based on diameter now 230

Variables and how each one contributes

NuD

Nusselt number

Result ·

What the equation gives you. Everything else feeds it.

ReD

Reynolds number based on diameter

· typical 10,000 to 1,000,000

The Reynolds number based on the tube diameter. Raises the Nusselt number as Re^0.8. Raising it by 10 % (to 110,000) moves the result by +7.92 %, from 230 to 248.2.

Pr

Prandtl number

· typical 0.7 to 160

The Prandtl number. Raises the Nusselt number as Prⁿ. Raising it by 10 % (to 1.1) moves the result by +3.89 %, from 230 to 238.9.

n

Exponent (0.4 heating, 0.3 cooling)

· typical 0.3 to 0.4

The Prandtl exponent: 0.4 for heating, 0.3 for cooling. A larger exponent gives a larger Nusselt number when Pr is above 1. Raising it by 10 % (to 0.44) moves the result by +0 %, from 230 to 230.

Worked example with the values above

  1. Reynolds term: Re^0.8 = 100,000^0.8 = 10,000.
  2. Prandtl term: Pr^n = 1^0.4 = 1.
  3. Nu = 0.023 × 10,000 × 1 = 230.

Assumptions and limits

  • Fluid properties are evaluated at the film or bulk temperature as stated, and are otherwise constant.
  • The geometry and flow regime match the correlation range, such as smooth tubes, single cylinders or isothermal plates.

Common mistakes

  • Using a correlation outside its Reynolds, Prandtl or Rayleigh range.
  • Using the wrong characteristic length, for example plate length instead of tube diameter.
  • Taking the properties at the wall or free-stream temperature when the film temperature is intended.

Statistics and uncertainty

Published correlations typically scatter by 10 % to 25 % against experiment, and the property evaluation temperature adds to the error. Use the result as an estimate to be confirmed by test for critical designs.

Where it is used

  • Estimating coefficients for heat sinks, ducts, tubes and walls.
  • Screening calculations before a detailed model or test.

Maths you need

  • Reynolds number: Re = ρUL/μ
  • Prandtl number: Pr = μcp/k
  • Nusselt number: Nu = hL/k

Related formulas