Resistance and temperature

Resistance of a conductor after a temperature rise, using a linear temperature coefficient.

Ref
ELE-05
Rev
v1
Field
Electrical
Result
R [Ω]

R0 is the resistance at the reference temperature, α the temperature coefficient of resistance in 1/°C, and θ the temperature rise above that reference in °C.

Most metals resist current more as they warm up. Over a modest range the rise is close to a straight line: the fractional change in resistance is the coefficient α times the temperature rise θ.

Calculator

Solve for
Ω
Ω
101,000
1/°C
5e-40.006
°C
0200
  • Change ΔR = R − R038.5 Ω
  • Fractional change38.5 %
  • Slope αR00.385 Ω/°C

What drives the result

Each variable is moved across its typical range while the others stay at the values above. The longest bar is the key driver.

Resistance at temperature (Ω) current value 138.5 Ω
R0Resistance at reference temperatureKey driver
13.81,390
θTemperature rise
100177
αTemperature coefficient
105160
  • Resistance rises as a straight line with θ and is directly proportional to R0. A Pt100 sensor (R0 = 100 Ω, α ≈ 0.00385) gains about 0.385 Ω per °C.
  • Heating raises the resistance of a metal conductor, so at a fixed current it dissipates more power and at a fixed voltage it dissipates less.
  • The straight-line model is an approximation. Over wide ranges the real curve bends, and standards such as IEC 60751 use a polynomial for platinum sensors.
Chart data as tables

Ranked variables

VariableTypical rangeLowest resultHighest resultSwing (Ω)Local stepChange in result
R0 Resistance at reference temperature10 to 1,000 Ω13.851,3851,371+10%+10 %
θ Temperature rise0 to 200 °C10017777+10%+2.78 %
α Temperature coefficient5e-4 to 0.006 1/°C10516055+10%+2.78 %

Sweep of Temperature rise

Temperature rise (°C)Resistance at temperature (Ω)
0100
25109.6
50119.2
75128.9
100138.5
125148.1
150157.8
175167.4
200177

Sweep one variable

Resistance at temperature (Ω)Hover, touch, or use the arrow keys on the chart
100120140160180 050100150200 Temperature rise (°C) now 138.5

Variables and how each one contributes

R

Resistance at temperature

Result · Ω

What the equation gives you. Everything else feeds it.

R0

Resistance at reference temperature

Ω · typical 10 to 1,000

Resistance measured at the reference temperature, often 0 °C or 20 °C. Directly proportional: R scales with R0 and the fractional change stays the same.

α

Temperature coefficient

1/°C · typical 5e-4 to 0.006

Fractional change in resistance per degree. About 0.0039 per °C for copper and 0.00385 for the platinum in Pt100 sensors. Negative for NTC thermistors. Sets the slope. A larger α means resistance changes faster with temperature, which makes a better temperature sensor but a larger heating effect in a power conductor.

θ

Temperature rise

°C · typical 0 to 200

Temperature above the reference temperature at which R0 and α apply. Linear: each extra degree adds αR0 ohms. Valid only while the straight-line approximation holds.

Worked example with the values above

  1. Fractional change: αθ = 0.00385 × 100 = 0.385.
  2. Factor: 1 + αθ = 1.385.
  3. R = R0(1 + αθ) = 100 × 1.385 = 138.5 Ω.

Assumptions and limits

  • Linear variation of resistance with temperature, valid over a limited range.
  • θ is measured from the reference temperature at which R0 and α are specified (often 0 °C or 20 °C).
  • Thermal expansion of the conductor is ignored.

Common mistakes

  • Using the absolute temperature instead of the rise above the reference temperature.
  • Using an α quoted at 20 °C with an R0 measured at 0 °C. The two must refer to the same reference.
  • Applying the formula to thermistors, whose resistance varies non-linearly and for NTC types falls as temperature rises.

Statistics and uncertainty

α is an empirical coefficient, usually quoted for a reference temperature and a given purity of material, and it carries a tolerance. For a sensor, the uncertainty in temperature follows from the uncertainty in resistance: δθ ≈ δR / (αR0). A ±0.1 Ω error on a Pt100 corresponds to about ±0.26 °C.

Where it is used

  • Resistance thermometers and temperature sensing.
  • Estimating the temperature rise of a copper winding from a resistance measurement.
  • Allowing for heating in cable and heater calculations.

Maths you need

  • Percentages and ratios: a fractional change αθ, then multiplied by R0
  • Units: θ in °C and α in 1/°C