Refrigeration coefficient of performance

Cooling delivered per unit of work put in.

Ref
THE-08
Rev
v1
Field
Thermodynamics
Result
COP

Use positive cycle energy magnitudes. QC is heat removed from the cold space and Win the work (or power) input. Energy balance gives QH = QC + Win.

A refrigerator moves heat from cold to hot; the COP is how much heat it removes for each unit of energy it uses.

Calculator

Solve for
kW
0.11,000
kW
0.1500
  • Heat rejected QH8 kW
  • Power per kW of cooling0.3333 kW/kW

What drives the result

Each variable is moved across its typical range while the others stay at the values above. The longest bar is the key driver.

Coefficient of performance () current value 3
QCCooling effectKey driver
0.05500
WinPower input
0.01260
  • A COP of 3 means 3 kW of cooling for 1 kW of electrical power, possible because the machine moves heat rather than making it.
  • The COP can exceed 1; efficiency cannot.
Chart data as tables

Ranked variables

VariableTypical rangeLowest resultHighest resultSwing ()Local stepChange in result
QC Cooling effect0.1 to 1,000 kW0.05500499.9+10%+10 %
Win Power input0.1 to 500 kW0.0126059.99+10%−9.09 %

Sweep of Power input

Power input (kW)Coefficient of performance
0.160
0.2920.69
0.84097.135
2.4382.461
7.0710.8485
20.50.2926
59.460.1009
172.40.0348
5000.012

Sweep one variable

Coefficient of performance ()Hover, touch, or use the arrow keys on the chart
0102030405060 0.1110100 Power input (kW), log scale now 3

Variables and how each one contributes

COP

Coefficient of performance

Result ·

What the equation gives you. Everything else feeds it.

QC

Cooling effect

kW · typical 0.1 to 1,000

Heat removal rate from the cold space. Directly proportional.

Win

Power input

kW · typical 0.1 to 500

Compressor power input. Inversely proportional.

Worked example with the values above

  1. Cooling effect QC = 6 kW.
  2. Work input Win = 2 kW.
  3. COP = 6 / 2 = 3.

Assumptions and limits

  • Steady operation.
  • Positive energy magnitudes.

Common mistakes

  • Treating COP as an efficiency below 100%.
  • Using heat rejected instead of cooling effect.

Statistics and uncertainty

Measured COP values from field tests typically carry ±5–10% because of load and ambient variation.

Where it is used

  • Cooling plant and air-conditioning sizing.
  • Equipment-cooling system checks.

Maths you need

  • Energy balance: QH = QC + W
  • Heat engine: reverse cycle