Complex power from voltage and current phasors

Real power P from RMS voltage and current phasors given in rectangular parts, with the current entering the load’s positive terminal.

Ref
ELN-42
Rev
v1
Field
Circuits, electronics and noise
Result
P [W]

With RMS phasors V = Vr + jVi and I = Ir + jIi, the complex power is S = V I* = P + jQ. Real power is P = Vr Ir + Vi Ii, and reactive power is Q = Vi Ir − Vr Ii, positive for an inductive load (current lagging). The apparent power is |S| = |V||I| and the power factor is P/|S|. The calculator returns P; the others are in the derived rows.

Real power P from RMS voltage and current phasors given in rectangular parts, with the current entering the load’s positive terminal. The reactive power Q (positive for an inductive load) and the apparent power are in the derived rows.

Calculator

Solve for
W
V
−500500
V
−500500
A
−5050
A
−5050
  • Reactive power Q400 var
  • Apparent power |S|500 VA
  • Power factor, P/|S|0.6
  • Phase angle between voltage and current53.13 °

What drives the result

Each variable is moved across its typical range while the others stay at the values above. The longest bar is the key driver.

Real power (W) current value 300 W
IrCurrent, real partKey driver
−5,0005,000
ViVoltage, imaginary part
−1,7002,300
VrVoltage, real part
−1,5001,500
IiCurrent, imaginary part
  • The load takes P = 300 W and Q = 400 var from an apparent power of 500 VA.
  • The power factor is 0.6; a positive Q means the current lags the voltage, as in a motor.
Chart data as tables

Ranked variables

VariableTypical rangeLowest resultHighest resultSwing (W)Local stepChange in result
Ir Current, real part−50 to 50 A−5,0005,00010,000+2 A+66.7 %
Vi Voltage, imaginary part−500 to 500 V−1,7002,3004,000+20 V−26.7 %
Vr Voltage, real part−500 to 500 V−1,5001,5003,000+20 V+20 %
Ii Current, imaginary part−50 to 50 A3003000+2 A0 %

Sweep of Current, real part

Current, real part (A)Real power (W)
−50−5,000
−37.5−3,750
−25−2,500
−12.5−1,250
00
12.51,250
252,500
37.53,750
505,000

Sweep one variable

Real power (W)Hover, touch, or use the arrow keys on the chart
−4000−2000020004000 −40−2002040 Current, real part (A) now 300

Variables and how each one contributes

P

Real power

Result · W

What the equation gives you. Everything else feeds it.

Vr

Voltage, real part

V · typical −500 to 500

The real part of the voltage phasor, in V. Raises the real power in proportion to Ir. Raising it by 10 % (to 110) moves the result by +10 %, from 300 to 330 W.

Vi

Voltage, imaginary part

V · typical −500 to 500

The imaginary part of the voltage phasor, in V. Raises the real power in proportion to Ii. Raising it by 10 % (to 0) moves the result by +0 %, from 300 to 300 W.

Ir

Current, real part

A · typical −50 to 50

The real part of the current phasor, in A. Raises the real power in proportion to Vr. Raising it by 10 % (to 3.3) moves the result by +10 %, from 300 to 330 W.

Ii

Current, imaginary part

A · typical −50 to 50

The imaginary part of the current phasor, in A. Raises the real power in proportion to Vi. Raising it by 10 % (to −4.4) moves the result by +0 %, from 300 to 300 W.

Worked example with the values above

  1. Real parts: Vr Ir = 100 × 3 = 300 W.
  2. Imaginary parts: Vi Ii = 0 × −4 = 0 W.
  3. P = 300 + 0 = 300 W.

Assumptions and limits

  • Sinusoidal steady state with RMS values, and a balanced three-phase load where stated.
  • Accurately connected meters in the standard two-wattmeter arrangement.

Common mistakes

  • Using Vr Ir − Vi Ii, which is the real part of the plain product V I and not of V I*.
  • Reversing the sign of Q by taking the wrong sign of the current angle.
  • Using peak phasors where RMS phasors are needed, which doubles the power.

Statistics and uncertainty

Meter errors, supply voltage fluctuation and unbalance all move these results. Wattmeter readings carry the meter’s accuracy class, and for the balanced-load formulas any unbalance gives an error, so check the readings against the total power.

Where it is used

  • Power-factor correction in plants and workshops.
  • Measuring power in three-phase motors and checking delta loads and cables.

Maths you need

  • RMS values: the equivalent steady value of an AC quantity
  • Real, reactive and apparent power: P, Q and S
  • Three-phase systems: line and phase quantities differ by √3